5 water system – Glow-worm Ultracom cx User Manual

Page 12

Advertising
background image

12

5 Water System

5.1 General

This boiler is designed for use as part of a sealed water

central heating system with fully pumped circulation. The

pump, expansion vessel and associated safety devices are all

fitted within the boiler.

5.2 Safety Valve

The safety valve is an integral part of the boiler and it cannot

be adjusted.

The pipe from the safety discharge valve must

not discharge above an entrance, window or any type of

public access area.

5.3 Expansion Vessel

The boiler has an integral expansion vessel with a capacity of

8 litres (1.76 gallons), with a charge pressure of 0.5bar.
NOTE: The expansion vessel volume depends on the total

water system volume and the initial system design pressure.

In GB, Guidance on vessel sizing is also given in the current

issue of BS5449 and BS7074 Part 1.
In IE, current edition of I.S.813 “Domestic Gas Installations”.

5.4 Flow Rate

If it is necessary to alter the flow rate, the system can be

fitted with a lockable balancing valve in the main flow or

return pipes shown as valve “A” in diagram 5.1. The flow rate

through the boiler must not be allowed to fall below that given

in section 1 - Specification Table.

5.5 Bypass

The boiler is fitted with an automatic bypass which can be

adjusted to suit your system requirements.
Ensure that under no circumstances does the flow rate drop

below the figure specified, refer to section 1 - Specification

Table.

5.6 Filling the Sealed System

The boiler is supplied with a filling device, see diagram 8.1.
This filling device is designed to enable the filling and

pressurisation of the system in the event of loss of pressure.
NOTE: The water pressure at the boiler must be at least

1.2bar to enable filling the boiler to a minimum pressure. If

not pressurisation must be carried out by an alternative filling

loop.
Suitable external filling systems are shown diagrammatically,

see diagram 5.2. The system should be pressurized to 1bar,

indicated on the digital display with no heating demand.

5.7 Draining Points

Draining taps must be provided at all low points of the system,

which will allow the entire system to be drained.
Draining taps shall be to the current issue of BS2879.
Drain points for the appliance are provided at the positions

shown in diagram 8.1.

Diagram 5.1

12800

5.8 Water Treatment

Existing system- It is ESSENTIAL that prior to installing the

new boiler the system is thoroughly flushed.
New system- For optimum performance after installation, the

boiler and its associated central heating system should also

be flushed.
Flushing should be carried out in accordance with BS7593:

2006 using a cleanser such as Sentinel X300 or X400, Fernox

Restorer or Salamander corrosion guard cleaner.
IMPORTANT: Ensure all cleanser is removed from the whole

system before adding an inhibitor.
For long-term corrosion protection, after flushing, an inhibitor

suitable for stainless steel exchangers should be used, refer

to the current issue of BS 5449 and BS 7593 on the use of

inhibitors in central heating systems. Examples are Sentinel

X100 Fernox Protector or Salamander corrosion guard

inhibitor.to the current issue of BS 5449 and BS 7593 on the

use of inhibitors in central heating systems. Examples are

Sentinel X100 Fernox Protector or Salamander corrosion

guard inhibitor.

Ensure all cleanser is removed from the system.

Advertising