11 electrical connection – Glow-worm Ultracom cx User Manual

Page 37

Advertising
background image

37

11.2 System Controls 24V

WARNING: UNDER NO CIRCUMSTANCES MUST

ANY MAINS VOLTAGE BE APPLIED TO ANY OF THE

TERMINALS ON THE 24V CONNECTION PLUG.
Connect the mains supply and system heating controls e.g.

room thermostat as diagram 11.2. External controls should be

fitted in accordance with the rules in force.

11.3 Mains Voltage System Controls

WARNING: UNDER NO CIRCUMSTANCES MUST

ANY MAINS VOLTAGE BE APPLIED TO ANY OF THE

TERMINALS ON THE 24V CONNECTION PLUG.
Connect mains supply and system controls as diagram 11.3.
External controls should be fitted in accordance with the rules

in force.

11.4 Electrical Cartridge Securing

Fit electrical cartridge into the interface housing on completion

of the wiring, see diagram 11.4.
Secure with the two cartridge retaining screws provided in the

cartridge body.

11.5 Electrical Connections - Testing

Carry out preliminary electrical system checks as below:
1. Test insulation resistance to earth of mains cables.
2. Test the earth continuity and short circuit of cables.
3. Test the polarity of the mains.
NOTE: If you require to test the appliance refer to section 14.

11 Electrical Connection

13488

Diagram 11.4

Advertising