Standard horizontal flue – Glow-worm Ultracom sxi User Manual

Page 23

Advertising
background image

23

13561

Standard Horizontal Flue

10.6 Flue Length

The maximum permissible horizontal flue length is 10 metres

plus the flue terminal assembly, this can be achieved by use

of the accessories, see diagram 10.12.
However should additional 87.5o or 2 x 45o elbows be used

then the length MUST be reduced by 1metre.
The diagram 10.10 shows the length achievable by using the

kit A2043400.
When extension pipes are used the flue system must be

designed to have a continuous fall to the boiler of at least 2.5o

44mm/metre to allow condensate to run back into the boiler

and out via the condensate drain.
The flue can be installed from inside the building, when

access to the outside wall face is not practicable.

Multiple Boiler Chimney Flue Length

The flue length must be calculated and installed according to

the relevant standards EN 13384-1 and 2 (C43 flue systems

only) with reference to the table below and the manufacturers

instructions supplied.
The appliance maximum flue length must be included when

calculating the overall design of the flue system.

NOTE: The

horizontal flue terminal must be removed, see diagram 10.11.

10 Standard Flue - Length, Preparation and Installation

Diagram 10.10

220

170

505mm

55mm

13560

MODEL

18sxi

30sxi

Exhaust mass rate (g/s)
At Min Thermal
Load (40C°/30°C)

2.30

2.45

At Max Thermal
Load (80C°/60°C)

8.75

13.25

Exhaust temperature (ºC)
At Min Thermal
Load (40C°/30°C)

56.0

44.0

At Max Thermal
Load (80C°/60°C)

69.0

57.0