10 Twin Flue - Length, Preparation and Installation

10.12 Twin flue

The twin flue system is available as an option when the top

horizontal or vertical flue system is not appropriate.
The system can provide an independent horizontal air inlet

and flue outlet, horizontal air inlet and vertical flue outlet or

vertical air inlet and flue outlet via a concentric terminal.
The system is made up from accessories, see diagram 10.26.
NOTE: The air and flue outlets do not have to be equal

lengths. 2x45° bends can replace 1x90° bend if necessary.
The maximum permitted combined (air inlet + flue outlet) flue

length is 40 metres plus terminal assemblies, for each 90°

or

45°

x 2 bends fitted, the maximum length must be reduced by

1 metre, see diagram 10.25.
NOTE: When using 90° bends any horizontal run should be

inclined by a minimum of 44mm/metre (2.5°) towards the

boiler to facilitate condense removal.
Alternatively use 45° bends to avoid horizontal runs in the flue

pipe.

Multiple Boiler Chimney Flue Length

The flue length must be calculated and installed according to

the relevant standards EN 13384-1 and 2 (C43 flue systems

only) with reference to the table below and the manufacturers

instructions supplied.
The appliance maximum flue length must be included when

calculating the overall design of the flue system.

Terminal Position

The clearances for a flue outlet are given in the "Flue Location

and Ventilation" section.
In addition the horizontal air inlet must not be closer than 300

mm from a flue outlet on the same wall or 1200mm from an

opposing flue outlet.

Diagram 10.26

14869

MODEL

18sxi

30sxi

Exhaust mass rate (g/s)
At Min Thermal
Load (40C°/30°C)

2.30

2.45

At Max Thermal
Load (80C°/60°C)

8.75

13.25

Exhaust temperature (ºC)
At Min Thermal
Load (40C°/30°C)

56.0

44.0

At Max Thermal
Load (80C°/60°C)

69.0

57.0