12.9 LPG CONVERSION - all models

As an option, a chargeable boiler only commissioning service

can be provided by Glow-worm Service by calling telephone

No. 01773 828100.
NOTE: Steps 12.1 and 12.3 will need to be completed before

the appliance can be converted.
This conversion should only be carried out by a

competent

person approved at the time by the Health and Safety

Executive.
During the conversion to Propane use of a suitable flue gas

analyser is necessary.
● The person carrying out a combustion measurement should

have been assessed as competent in the use of a flue gas

analyser and the interpretation of the results.
● The flue gas analyser used should be one meeting the

requirements of BS7927 or BS-EN50379-3 and be calibrated

in accordance with the analyser manufacturers’ requirements.
● Competence can be demonstrated by satisfactory

completion of the CPA1 ACS assessment, which covers

the use of electronic portable combustion gas analysers in

accordance with BS 7967, parts 1 to 4.
As an option a chargeable boiler only commissioning service

can be provided by Glow-worm Service by calling telephone

No. 01773 828100.
Tools required to make the conversion are a 2mm Allen key

and an electricians screwdriver.
Ensure that the appliance supply pressure = 37mbar.
(1) Access the gas valve.
(2) Refer to diagram 12.5 and turn the gas valve throttle

fully clockwise.

(3) Turn the throttle anti-clockwise by the number of turns

shown in the table.

(4) Ensure that the gas analyser is set to the correct

fuel setting - Propane.

(5) Attach combustion analyser to the combustion test point,

refer diagram 13.1.

IMPORTANT: Remember to replace the cap on

completion of the test.

(6) Make sure that the external controls are calling for heat,

then turn the mains electrical supply and gas service

isolation valve on.

(7) Switch the boiler on. The boiler should fire automatically.

NOTE: If the appliance does not light and goes to

lockout (F1) turn the throttle anti-clockwise a further turn

and press the reset button. The appliance will (after a

short delay) again attempt to fire. Repeat this procedure

(up to a total of 2 extra turns on the throttle screw) until

the appliance lights. Several ignition attempts may be

needed, to purge gas through the appliance, before a

successful ignition is achieved.

(8) Check and adjust the burner %CO2 at maximum rate.

Press the “reset” button on the controls fascia, release

and immediately press and hold in the “+” button. After

approximately 5 seconds “Hi” will be displayed. Pressing

the mode button when “Hi” is selected will force the

boiler to maximum rate, the display will flash between

“Hi” and the “default display” this will indicate the boiler

has been forced to maximum.

12 Commissioning - Nat. Gas (G20) to LPG (G31) Conversion

OFFSET

ADJUSTMENT

THROTTLE

ELECTRICAL

PLUG

GAS PIPE

RETAINING

CLIP

SEALING

GROMMET

13553

Diagram 12.5

13870

(9) If necessary, adjust the burner % CO2 to the value shown

in the “SETTING” column of the table, by turning the

throttle screw (anti- clockwise to increase), see diagram

12.5 no more than 1/8 of a turn, waiting a minute to allow

for the appliance to stabilise before checking or making

further adjustments.

(10) Exit the check sequences press the “mode” and “+”

buttons simultaneously, this will reset the boiler to the

default display.

(11) Check the burner % CO2 , at minimum rate, to the value

shown in the “SETTING” column of the table.

(12) If adjustment is required, press the “reset” button on the

controls fascia, release and immediately press and hold

in the “+” button. After approximately 5 seconds “Hi” will

be displayed. Pressing the “+” or “-” buttons will cycle

between “Hi” and “Lo”. Pressing the mode button when

“Lo” is selected will force the boiler to minimum rate, the

display will flash between “Lo” and the “default display”

this will indicate the boiler has been forced to minimum.

(13) Adjustment of the %CO2 is very coarse so carefully adjust

the %CO2 to the value shown in the “SETTING” column

of the table with the offset adjustment, see diagram 12.5

and %CO2 Table (Rotate clockwise to increase).

(14) To exit the function press the “mode” and “+” buttons

simultaneously, this will reset the boiler to the

default display.

(15) Repeat (8) and check CO2 at maximum rate - adjust if

necessary. Check that the CO/CO2 ratio is less than the

value in the table below.

(16) Remove analyser probe from the test point and replace

the cap. Refit the control panel.

(17)

IMPORTANT: Fit the LPG conversion label supplied

in the documentation pack to the inner front panel

alongside the data label. Refit the inner door and outer

door.

(18) Continue commissioning from 12.4.