3 evacuation of combustion gas – Glow-worm Ultrapower sxi User Manual
Page 13

13
3 Evacuation of Combustion Gas
3.2 Flue configuration description
3.2.1
Horizontal concentric flue Ø 60/100 mm
or Ø 80/125 mm (C13 type installation)
a
If the terminal is at less than 1.80 m from the
ground, you must install a terminal protection
kit.
Ø 60/100 mm
L
63
1
Key
1 Gasket (fitted)
Ø 80/125 mm
L
1
Key
1 Gasket (fitted)
Type
Max length
Ø 60/100
8 m
Ø 80/125
25 m
Each time an additional 90° bend is necessary (or 2 at 45°),
the length (L) must be reduced by 1 m.
3.2.2
Vertical concentric flue Ø 60/100 mm
or Ø 80/125 mm (C33 type installation)
a
If the terminal is at less than 1.80 m from the
ground, you must install a terminal protection
kit.
L
Type
Max length (L)
Ø 60/100
12 m
Ø 80/125
25 m
Each time an additional 90° bend is necessary (or 2 at 45°),
the length (L) must be reduced by 1 m.