10 electrical connection – Glow-worm Ultrapower sxi User Manual

Page 24

Advertising
background image

24

WARNING: This appliance must be earthed.
● This appliance must be wired in accordance with these

instructions. Any fault arising from incorrect wiring cannot be

put right under the terms of the Glow-worm guarantee.
● All system components must be of an approved type.
Electrical components have been tested to meet the

equivalent requirements of the BEAB.
● Do not interrupt the mains supply with a time switch or

programmer.
● Connection of the whole electrical system and any heating

system controls to the electrical supply must be through a

common isolator.
● Isolation should preferably be by a double pole switched

fused spur box having a minimum contact separation of

3mm on each pole. The fused spur box should be readily

accessible and preferably adjacent to the boiler. It should be

identified as to its use.
● A fused three pin plug and shuttered socket outlet may be

used instead of a fused spur box provided that:
a) They are not used in a room containing a fixed bath or

shower.
b) Both the plug and socket comply with the current issue of

BS1363.

10 Electrical Connection

Immersion Heater

- the thermostatically controlled

immersion heater with manual reset is fitted to the cylinder

as a back up for domestic hot water in the event of the boiler

being inoperable, it MUST be wired separately from the boiler

electrical connections.
The heater should be wired through a double-pole switch or

controller having a minimum contact separation of 3mm on

each pole. Use a cable size of at least 1.5sq. mm flexible

cable, 85 deg.C rubber insulated HOFR sheathed to comply

with BS6141 Table 8 and must be fully earthed.