INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the
I-13-EM-J unit connector is disconnected.

1. MOUNTINg ThE I-13-EM-J

When used with ceiling mounted downlight fixtures, the

I-13-EM-J should be mounted on the fixture above

the ceiling.

When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between

the battery pack and the lamp.

2. MOUNTINg ThE TEST SWITCh AND ChARgE INDICATOR LIghT

Cut a single gang switch box into the ceiling tile adjacent to the fixture within reach of the

I-13-EM-J flex. After

mounting the switch box, connect flex to the box and route all leads inside the box. Connect the leads to the com-
ponents as follows:

Red lead

(+) Charge light terminal

Wht/Red lead (–) Charge light terminal

White

Test

switch

*Wht/Blk

lead

Unit

connector

White/Black

*Wht/Blk lead Unit connector

* To prevent electrical shock and unintentional battery discharge, do not join the unit connector until the installation

is complete.

NOTE: To ensure proper operation, use only the test accessories provided with the unit. See Page 1 of the Instruc-

tion Manual.

3. WIRINg

A.

The

I-13-EM-J and A.C. ballast must be on the same branch circuit.

B.

The

I-13-EM-J requires an unswitched A.C. power source of either 120 or 277 volts; therefore, when used with

switched fixtures, the

I-13-EM-J input must be wired ahead of the switch.

C. Refer to the wiring diagrams on the back page for the proper wiring.

4. LABELS

Attach the appropriate labels adjacent to the

Test Switch and Charge Indicator. Annotate Re-lamping label for

lamp type and wattage. The Caution and the Re-lamping labels must be on the fixture in a readily visible location
to anyone attempting to service the fixture.

5. COMPLETINg INSTALLATION

When the installation is complete, switch the A.C. power on and join the

I-13-EM-J unit connector.

INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.