Page 2

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the ICE-80 unit connector is disconnected.

1. LAMPS OPERATED

The

ICE-80 can be used with most

2

′–8′ lamps. Refer to the chart below for the type of lamp(s) operated and the num-

ber of lamps to be operated in emergency mode.

*The 6

″ violet leads provide the lamp selection option. The unit is shipped from the factory with the leads

disconnected and capped. When used with particular lamp types, violet leads should be connected to one anoth-
er. Refer to chart for lamp selection options.

2. MOUNTING THE ICE-80

Remove the ballast channel cover. Mount the

ICE-80 in the ballast channel at least

1

/

2

″ away from the A.C.

ballast(s).

When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between

the battery pack and lamp(s).

3. WIRING

Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance

with the National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.

4. INSTALLING THE CHARGE INDICATOR

Recessed Troffer Fixture – Select a convenient location with proper clearance in the ballast cover and drill or

punch a

7

/

8

″ hole (½″ knockout). Insert the

7

/

8

″ bushing into the hole. Push the plastic tube through the bushing.

Disconnect the leads from the

LED housing and route the leads down the plastic tube. Reconnect the leads to the

housing, observing the proper polarity (Red/Black or Red lead w/connector to positive (+) red tab). Push the entire

assembly back into the tube until the lens collar rests against the plastic tube. The plastic tube should be adjusted

so that the

Charge Indicator is within ¼

″ of the fixture lens. The Charge Indicator must be visible after installa-

tion. Refer to Illustration 1.

Strip Fixture – Select a convenient location on the side of the fixture so the

Charge Indicator can be seen after

installation. Allow for proper clearance inside the fixture and drill or punch a ½

″ hole. Disconnect the leads from

the

LED housing. Push the LED housing into the

1

/

2

″ hole until it is firmly locked in place. Reconnect the leads,

observing the proper polarity (Red/Black or Red lead w/connector to positive (+) red tab). Refer to Illustration 2.

OPTION

LAMP TYPE

EMERGENCY

OPERATION

*VIOLET LEADS

WIRING

DIAGRAMS

1

2

3

4

5

2´-4´ T8/T12 Single & Bipin Pin

5´-8´ T8/T12 Single & Bipin Pin

2´-4´ T8/T12 Single & Bipin Pin

2´-4´ 28W-39W T5

2´-4´ 54W T5

One Lamp

One Lamp

Two Lamp

One Lamp

One Lamp

Connected

Disconnected

Disconnected

Connected

Disconnected

1, 2, 3, 4, 5, 6, 7, 8

1, 2, 3, 5, 6

1, 2, 3, 4, 5, 6, 7, 8

1, 2, 3, 4, 5, 6, 7, 8

6

18W-55W Long Compact

One Lamp

Disconnected

1, 2, 3, 4, 5, 6, 7, 8

5. INSTALLING THE TEST SWITCH

The test switch should be mounted on the ballast channel cover of a recessed troffer, or on the side of a strip

fixture, preferably adjacent to the charge indicator. Drill or punch a ½

″ mounting hole.

7/8" BUSHING

FIXTURE

BALLAST CHANNEL COVER

PLASTIC TUBE

CHARGE INDICATOR
LIGHT

FIXTURE LENS

Illustration 1 Recessed Troffer Fixture

FIXTURE

CHARGE

INDICATOR

LIGHT

(POS LEAD)
RED/BLK OR
RED W/CONNECTOR

WHITE/RED

LEAD

+ RED

Illustration 2 Strip Fixture

ICE-80

OBSERVE PROPER POLARITY

ICE-80

Advertising