Figure 1, Page 3 – IOTA IIS-125-SM User Manual

Page 3

Advertising
background image

Page 3

IIS_125_375_UPDATE.EPS

INVERTER - INTERRUPTIBLE

120V

277V

LOCAL SWITCH

(IF PRESENT)

ALTERNATE

AC INPUT

INVERTER

WHT (NEUTRAL)

ORG (277V)

BLK (120V)

FLYING LEADS

GROUND

WIRE

AC INPUT - SELECT PROPER VOLTAGE
LEAD AND CAP UNUSED LEAD.

GROUND WIRE - CONNECT FIXTURE SUPPLY
GROUND AND UNIT GROUND IN ACCORDANCE
WITH LOCAL AND NATIONAL CODES.

IF USING A SECONDARY AC INPUT, SELECT
PROPER VOLTAGE LEAD AND CAP UNUSED
LEAD.

USE A 277V RATED SWITCH IF CONNECTING
TO 277V INPUT.

FLYING LEADS - SELECT PROPER VOLTAGE
LEAD AND CAP UNUSED LEAD.

YELLOW (277V)

VIOLET (120V)

GRAY (NEUTRAL)

GREEN

NORMAL CIRCUIT

EMERGENCY CIRCUIT

NORMAL

LIGHTING LOAD

DESIGNATED

EMERGENCY LOAD

INPUT LEADS

ORG (277V)

BLK (120V)

WHT (NEU)

OUTPUT LEADS

BRANCH

CIRCUIT

OPERATES IN BOTH NORMAL AND

EMERGENCY MODES. CIRCUIT MUST BE

ISOLATED FROM NORMAL CIRCUITS.

FIGURE 1 -

IIS-125 WIRING CONNECTIONS

2. CONNECTING REMOTE EMERGENCY FIXTURES (FIGURE 1)
A. Connect remote emergency fixtures to the correct output leads. The color code is as follows: neutral is Gray, 120V
is Violet, and 277V is Yellow. All remote circuitry is to be wired in accordance with Article 700 of the National
Electric Code. Do not exceed the total rating of the

IIS-125. When making connections to the IIS-125, DO NOT

connect the Input Neutral (WHITE) to the Output Neutral (GRAY).

B. NORMALLY-OFF FIXTURES (only come on during power failure) - Connect the AC line input wire of the fixtures

to the appropriate output wires as above (120V or 277V). Connect the fixture Neutral input wire to the Neutral
output wire. Refer to

Figure 1.

C. NORMALLY-ON FIXTURES - Follow Step 2B above. Then select the proper voltage flying lead from the printed

circuit board (BLACK for 120V, ORANGE for 277V) and connect to the unswitched AC input line feeding the
transformer. Connect the Neutral (WHITE) flying lead coming from the printed circuit board to the unswitched AC
input neutral of the supply line feeding the input wires. Refer to

Figure 1.

D. FIXTURES ON LOCAL SWITCH (fixtures may be turned on and off locally, but will come on during power failure

regardless of switch position) - Follow Step 2B above. Connect the line side of the Switch to the unswitched
AC input line connected to the transformer. Connect the load side of the Switch to the proper voltage flying lead
from the printed circuit board (BLACK for 120V, ORANGE for 277V). Refer to

Figure 1. CAUTION: If connected

to 277 volt input, use a 277V rated switch. Failure to use the proper voltage switch may result in switch
failure, a shock hazard, an unsafe condition and equipment failure.

E. ALTERNATE FEED (all fixtures are supplied on normal from an alternate circuit) - Follow Step 2B above. Then extend

alternate AC input to the proper voltage flying leads from the printed circuit board (BLACK for 120V, ORANGE for
277V). If a local Switch is present, connect the alternate AC input to the Switch, then connect the proper voltage
flying leads from the printed circuit board to the load side of the Switch as in Step 2D. Refer to

Fig 1.

Consult

the

IIS-125

Application Notes for connecting the unit to specific lighting loads. Application Notes are

available on the internet or through Customer Service.

F. Connect the Fixture Supply Ground to the

IIS-125 Ground.

CAUTION: Before proceeding to Wiring Step 3, make sure that all unused wires are properly capped. Failure
to do so may result in an unsafe condition and equipment failure.

DO

NOT

ENERGIZE THE CIRCUIT AT THIS TIME.

3. INSTALLING THE BATTERIES

Use only battery part number

F741250003 with the unit. See Page 1 of this instruction manual.

A. Retaining brackets are provided. The batteries MUST be secured in the IIS-125. Do not leave the batteries

loose or unsecured within the unit.

B. Connect the batteries by plugging the connector into the receptacle on the PCB. If the batteries are not provided

with a connector, the PCB is equipped with Red and Black wires with ring terminals. Wire the Red wires to the
Positive terminals and the Black wires to the Negative terminals. Torque hardware to 33 in/lbs.


NOTE: Failure to connect or secure the batteries properly will result in equipment failure, an unsafe condition, and
will void the warranty.

NOTE: The emergency indicator lights will not illuminate at this time.