4. COMPLETING INSTALLATION
A. Energize the AC supply. Only the Ready (Yellow) Indicator and the Charging (Red) Indicator will illuminate.

B. Operate the Test Switch for approximately 10 seconds. Observe that any emergency fixtures do not go out, that

the Inverter On (Green) Indicator comes on, and that any normally off fixtures come on. Release the Test Switch.
Normally Off fixtures and the Inverter On (Green) Indicator will extinguish. Normally On, emergency, and any
switched fixtures will return to their normal operating mode.

C. Properly re-install the cover of the

IIS-125 using all the original hardware.

D. Affix red “EMERGENCY CIRCUIT” label (provided) to the panelboard dead front cover near the circuit breaker

feeding the

IIS-125.

3.

OPERATION

Normal Mode - AC power is present and operates the fixtures as intended. The IIS-125 is in the standby charging
mode. The Ready (Yellow) Indicator and Charging (Red) Indicator will be lit providing a visual indication that the unit
is charging.

Emergency Mode - The AC power fails. The IIS-125 senses the AC power failure and automatically switches to
the Emergency Mode. All fixtures, including Normally Off or switched off fixtures, connected to the

IIS-125 will be

illuminated for the duration required by national safety codes (minimum 90 minutes in US, minimum 30 minutes in
Canada). When the AC power is restored, the

IIS-125 switches the system back to the Normal Mode and resumes

battery charging. See page 1 of the instruction manual.

4.

TESTING

1) To test the equipment, depress the test switch. The Ready (Yellow) Indicator will go off. The designated fixtures will

either illuminate if they were off or will stay on if they were normally illuminated. The Inverter On (Green) Indicator
will come on.

2) Release the Test Switch. The Ready (Yellow) Indicator will come on. Normally Off emergency fixtures will extinguish.

The equipment is supplied with an automatic solid state charger designed to fully recharge the batteries within 48

hours after AC power is restored, and then maintain the batteries in a fully charged state. Allow the batteries to
charge for a minimum of 48 hours after installation or power failure before conducting a prolonged discharge test.
Monthly and annual testing should be performed in accordance with NFPA 101, local, state or municipal code re-
quirements.

“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”

5.

MAINTENANCE

1) CAUTION: Always turn off the AC supply to the equipment, and disconnect the battery before servicing. Only

qualified service technicians should service this equipment. The use of parts supplied by other than IOTA Engi-
neering, LLC may result in an unsafe condition, equipment failure and will void the warranty.

2)

BATTERY - The battery supplied in this equipment is a high quality maintenance-free Valve Regulated Lead Acid

design. It requires no maintenance and when installed in an ambient temperature of 20°-30° C (68°-86° F) its life
expectancy is 8 to 10 years. However, as stated above, the equipment must be tested for 90 minutes a minimum
of once per year. When the battery will no longer operate the load for 90 minutes it must be replaced. Replace
only with IOTA Engineering, LLC supplied parts. Dispose or recycle the lead-acid battery properly.

CONTACT CUSTOMER SERVICE FOR REPLACEMENT PARTS.

SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.