Fireplace installation – Desa (V)G36 User Manual

Page 5

Advertising
background image

www.desatech.com

116010-01C

5

HEARTH ExTENSION

A hearth extension projecting a minimum of 20"

in front of and a minimum of 12" beyond each

side of the fireplace opening is required to protect

combustible floor construction in front of the fire-

place. Fabricate a hearth extension using a material

which meets the following specifications: a layer

of noncombustible, inorganic material having a

thermal conductivity of K=0.84 BTU IN/FT, HR.

F (or less) at 1" thick. For example, if the material

selected has a K factor of 0.25, such as glass fiber,

the following formula would apply:

0.25 x 1.0" = 0.30" thickness required

0.84

Thermal conductivity "K" of materials can be

obtained from the manufacturer or supplier of the

noncombustible material. If the hearth extension

is to be covered, use noncombustible material such

as tile, slate, brick, concrete, metal, glass, marble,

stone, etc. Provide a means to prevent the hearth

extension from shifting and seal gap between the

fireplace frame and hearth extension with a non-

combustible material (see Figure 3).

WARNING: Hearth extension

is to be installed only as shown

in Figure 3.

Fireplace inSTallaTion

Continued

Figure 3 - Hearth Extension

Seal Gap

Fireplace Front

Ember Protector

Fireplace Front
Raised Hearth

Fireplace Front
Elevated

Ember Protector

Ember Protector

Seal Gap

Hearth

Extension

MANTELS

A mantel may be installed if desired (see Figure 4).

Woodwork such as wood trims, mantels or any other

combustible material projecting from the front face

must not be placed within 12" of the fireplace open-

ing. Combustible materials above 12" and projecting

more than 1

1

/

2

" from the fireplace must not be placed

less than 15" from the top opening of the fireplace

(NFPA STD 211, Sec. 7-3.3.3).

Mantels or any other combustible material also

may come up to the side edge of the black metal

face of the fireplace just as long as the projection

from the front face fall within the limit shown in

Figure 4.

1

1

/

4

" Ref.

15" Min.

1" Min.

1

1

/



" Max.

3" Nom.

33°

Combustible
Material

Safe
Zone for
Projection of
Combustible
Materials

Fireplace
Opening

Upper

Section of

Fireplace

Figure 4 - Mantel Clearances to

Combustible Material

FIREBOX

SAFE ZONE

Top View of Fireplace

3" Max.

4.5"

Min. to

Perpendicular

Side Wall

1"

7.75"

33°

Combustible
Material Must
Not Overlap
Front Face

6"

Ref.