VenTing inSTallaTion

Continued

Figure 9 - Elbow Offset

B

A

Screws

FIRESTOP SPACERS (1100EFS-10DM)

Firestop spacers are required at each point where

the chimney penetrates a floor space. Their purpose

is to establish and maintain the required clearance

between the chimney and the combustible materials.

When the pipe passes through a framed opening into

a living space above, the firestop must be placed onto

the ceiling from below as shown in Figure 10.

They also provide complete separation from one floor

space to another or attic space as required by most

codes. When the double wall pipe passes through a

framed opening into an attic space, the firestop must

be placed into an attic floor as shown in Figure 11.

Figure 10 - Firestop Spacer with Living

Space Above Ceiling

Figure 11 - Firestop Spacer with Attic

Space Above Ceiling

Existing
Ceiling
Frame

Firestop
Spacer

Screws or
Staples
(Min. of 8)

Firestop
Spacer

Screws or Staples
(Min. of 8)

PENETRATING THE ROOF

To maintain a 1" clearance to the pipe on a roof

with a pitch, a rectangular opening must be cut.

1. Determine the center point through which the

pipe will penetrate the roof.

2. Determine the center point of the roof. Pitch

is the distance the roof drops over a given

span, usually 12". A 6/12 pitch means that

the roof drops 6" for each 12" one measure

horizontally down from the roof rafters.

3. Use the roof opening chart (Figure 12) to

determine the correct opening length and

flashing required.

4. Remove the shingles around the opening

measured. Cut out this section.

5. Add the next sections of the pipe until the

end penetrates the roof line. Check to see that

the proper clearances are maintained. Extend

chimney by adding sections of double wall

pipe until pipe is minimum of 30" above the

highest point of the roof cutout. Termination

and chimney must extend a minimum of

36" above the highest point where it passes

through the roof.

17" Min.

30" Min.

1" Min.

1" Min.

1" Min.

Opening "A"

Pitch

Slope

Opening

"A" Max.

Used Flashing

Model No.

Flat

17"

V6F-10DM

0-6/1

6.6°

19"

V6F-10DM

6/1-

1/1

45.0°

4"

V12F-10DM

Existing
Ceiling
Frame

Figure 12 - Roof Opening Measurements