FLASHING INSTALLATION (V6F-10DM
OR V12F-10DM)

Determine the flashing to be used with the roof

opening chart. Slide flashing over pipe until base

is flat against roof. Replace as many shingles as

needed to cover exposed area and flashing base.

Secure in position by nailing through shingles

(see Figure 13). DO NOT NAIL THROUGH

FLASHING CONE.

Nail Only
Outer
Perimeter
of Flashing

Storm
Collar

Flashing
Cone

Underlap
Shingles
at Bottom

Overlap
Shingles Top
and Sides Only

Figure 13 - Flashing Installation

Installing Flashing on a Metal Roof

When installing the flashing on a metal roof, it is

required that putty tape be used between the flash-

ing and the roof. The flashing must be secured to

the roof using #8 x 3/4" screws and then sealed

with roof coating to prevent leakage through the

screw holes. A roof coating must also be applied

around the perimeter of the flashing to provide a

proper seal.
Storm Collar Installation (SC2-1)

Place storm collar over pipe and slide down until

it is snug against the open edge of the flashing (see

Figure 14). Apply waterproof caulk around the

perimeter of the collar to provide a proper seal.

Figure 14 - Storm Collar

Chimney
Pipe

Waterproof
Caulk

Storm
Collar

Flashing

Terminations/Spark Arrestor

The fireplace system must be terminated with the

listed round top or chase terminations. In any case,

refer to the installation instructions supplied with

the termination.

CAUTION: Do not seal open-

ings on the rooftop flashing. Fol-

low the installation instructions

provided with the termination

being used.

Secure
Termination
to Outer
Pipe with 3
Screws

RTL-10D

Level of
Flue Gas
Outlet

Stainless
Inner Flue
Pipe

Waterproof
Caulking

Storm
Collar

Flashing

Underlap
Shingles

Figure 15 - Termination

Overlap
Shingles (Top
and Sides of
Flashing Base)

CHASE INSTALLATIONS

Instructions for chase installations are included

with the chase style termination chosen. In a

multiple chase installation, be sure to provide

adequate distance between terminations to prevent

smoke spillage from one termination to another.

We suggest that terminations be separated at least

24" center to center and stacked at a vertical height

difference of 18" (see Figure 16, page 10).
Note:

If a decorative shroud is to be installed,

contact the manufacturer for specifications.