Elevation view of indicator post and valve, Field adjustment instructions – NIBCO NIP-1AJ Indicator User Manual

Page 2

Advertising
background image

A H E A D O F T H E F L O W

®

www.nibco.com

NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227

TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455

www.nibco.com

2

ELEVATION VIEW OF INDICATOR POST AND VALVE

17-4 Kennedy Valve/Indicator Posts

1

1

/

4

" Sq.

1" Sq. Stem

9"

36

3

/

4

"

5

1

/

8

"

30"

6" Dia.

12" Dia.

Trench

Depth

Ground Line

Standpipe

(painted red)

Standpipe

(painted black)

Top Section

max. = 10"

min. = 7"

INDICATOR POST STYLE 2945

FIXED LENGTH UL/FM

DIMENSIONS AND INSTRUCTIONS

KENNEDY VALVE

Available in Sizes F G H

See Page 6 for Dimensions

FIELD ADJUSTMENT

INSTRUCTIONS

1. Remove the top section from the top of the

Indicator Post assembly.

2. Cut the required length off the bottom of the

Standpipe for the Ground Line to match up

with Standpipe Ground Line mark.

3. Cut the 1" Sq. Stem at a distance of 9"

above the top of the Standpipe.

4. Set the “OPEN” and “SHUT” targets for the

appropriate valve size.

5. Reattach the Top Section to the top of the

Indicator Post assembly.