Troubleshooting – Desa CGFP28PT User Manual

Page 22

Advertising
background image

22

103414

UNVENTED PROPANE/LP GAS FIREPLACE

CGFP28P and CGFP28PT

OBSERVED PROBLEM

When ignitor button is pressed, there is no
spark at ODS/pilot

When ignitor button is pressed, there is
spark at ODS/pilot but no ignitio

ODS/pilot lights but flame goes out when
control knob is released

TROUBLESHOOTING

Note:

All troubleshooting items are listed in

order of operation.

WARNING: Turn off fireplace

and let cool before servicing. Only
a qualified service person should
service and repair fireplace.

CAUTION: Never use a wire,

needle, or similar object to clean
ODS/pilot. This can damage ODS/
pilot unit.

POSSIBLE CAUSE

1. Ignitor cable pinched or wet

2. Ignitor electrode not connected to igni-

tor cable

3. Piezo ignitor nut is loose

4. Broken ignitor cable
5. Ignitor electrode broken
6. Bad piezo ignitor
7. Ignitor electrode positioned wrong

1. Gas supply turned off or manual shutoff

valve closed

2. Control knob not in PILOT position
3. Control knob not pressed in while in

PILOT position

4. Air in gas lines when installed

5. ODS/pilot is clogged

6. Gas regulator setting is not correct

1. Control knob not fully pressed in
2. Control knob not pressed in long enough

3. Manual shutoff valve not fully open
4. Thermocouple connection loose at con-

trol valve

5. Pilot flame not touching thermocouple,

which allows thermocouple to cool,
causing pilot flame to go out. This prob-
lem could be caused by one or both of
the following:
A) Low gas pressure
B) Dirty or partially clogged ODS/pilot

6. Thermocouple damaged
7. Control valve damaged
8. On thermostat models, safety interlock

system has been triggered

REMEDY

1. Free ignitor cable if pinched by any

metal or tubing. Keep ignitor cable dry

2. Reconnect ignitor cable

3. Tighten nut holding piezo ignitor to base

panel of log set. Nut is located behind
base panel.

4. Replace ignitor cable
5. Replace ignitor
6. Replace piezo ignitor
7. Replace ignitor

1. Turn on gas supply or open manual

shutoff valve

2. Turn control knob to PILOT position
3. Press in control knob while in PILOT

position

4. Continue holding down control knob. Re-

peat igniting operation until air is removed

5. Clean ODS/pilot (see Cleaning and

Maintenance, page 21) or replace ODS/
pilot assembly

6. Replace gas regulator

1. Press in control knob fully
2. After ODS/pilot lights, keep control

knob pressed in 30 seconds

3. Fully open manual shutoff valve
4. Hand tighten until snug, then tighten

1/4 turn more

5. A) Contact local natural gas company

B) Clean ODS/pilot (see Cleaning
and Maintenance
, page 21) or replace
ODS/pilot assembly

6. Replace thermocouple
7. Replace control valve
8. Wait one minute for safety interlock sys-

tem to reset. Repeat ignition operation

Note:

For additional help, visit DESA

International's Technical Service web
site at

www.desatech.com

.

www.desatech.com

Advertising