Electrical data, Compressor protection module – WaterFurnace Envision2 NXW Chiller User Manual

Page 15

Advertising
background image

15

ENVISION

2

NXW REVERSIBLE CHILLER INSTALLATION MANUAL

Electrical Data

Model

Rated

Voltage

Voltage

Min/Max

Compressor

1

Total

Unit
FLA

Min

Circ

Amp

Min

Fuse/
HACR

Max

Fuse/

HACR

2

MCC

RLA

LRA

120

208-230/60/3

187/253

36.0

23.1

160.0

46.2

52.0

60.0

70

460/60/3

414/506

19.0

12.2

87.0

24.4

27.5

30.0

35

575/60/3

517/633

13.5

8.7

62.0

17.4

19.6

20.0

25

380/60/3

342/418

19.0

12.2

95.0

24.4

27.5

30.0

35

180

208-230/60/3

187/253

45.0

28.8

235.0

57.6

64.8

70.0

90

460/60/3

414/506

19.0

12.2

110.0

24.4

27.5

30.0

35

575/60/3

517/633

16.5

10.9

95.0

21.8

24.5

25.0

35

240

208-230/60/3

187/253

52.2

35.2

250.0

70.4

79.2

80.0

110

460/60/3

414/506

27.0

19.2

140.0

38.4

43.2

45.0

60

575/60/3

517/633

19.1

14.5

100.0

29.0

32.6

35.0

45

360

208-230/60/3

187/253

75.0

48.1

351.0

96.2

108.2

110.0

150

460/60/3

414/506

38.6

24.7

197.0

49.4

55.6

60.0

80

575/60/3

517/633

35.0

22.4

135.0

44.8

50.4

60.0

70

380/60/3

342/418

51.0

32.7

239.0

65.4

73.6

80.0

100

600

460/60/3

414/506

62.0

39.7

260.0

79.4

89.3

100.0

125

575/60/3

517/633

45.0

28.8

210.0

57.6

64.8

70.0

90

380/60/3

342/418

72.0

46.2

310.0

92.4

104.0

110.0

150

HACR circuit breaker in USA only

1

- MCC, RLA, & LRA rating per compressor. Breaker & FLA sized for both compressors.

2

- Equipment supplied with Class J fuses per minimum fuse size.

3/5/14

Compressor Protection Module

An electronic protection module is provided with

compressors utilized in model size 600. This module will
protect against phase reversal and phase loss at start-up.
Protection is active for 5 seconds after the first second
of compressor operation. In the event that either phase
sequencing or phase loss has occurred the following
blink sequence will display on the module.