Control features, Field wiring and control setup cont, Field selectable options – WaterFurnace Envision2 NXW Chiller User Manual
Page 20: Control and safety features
 
20
ENVISION
2
NXW REVERSIBLE CHILLER INSTALLATION MANUAL
Field Wiring and Control Setup cont.
Accessory Relay Setup
The accessory output set to “close” upon Y1 compressor call 
(compressor is delayed 90 sec. after Y1) but can be set to 
“open” with Y1.
To change ACC1:
• Using up and down keys, scroll to “Acc 1 Sel” hit “ENTER” 
and “ON Comp” begins flashing
• Using up and down keys, select “ON Comp” for activation
with Y1 Call or “OFF Comp” for deactivation with Y1
Lead/Lag Selection
Compressor Lead/Lag Selection is factory set to “ON” but 
can be set to “OFF”.
To change Lead/Lag On/Off:
• Using up and down keys, scroll to “LEAD/LAG SELECT” 
hit “ENTER” and “ON” begins flashing
• Using up and down keys, select “ON” for activation or “
OFF” for deactivation
Anti Short Cycle
High Pressure Protection
Low Pressure Protection
Advanced Freeze Detection Setpoint
Random Start 
Display for diagnostics
Reset Lockout at disconnect
Intelligent reset for field installed flow switches
1 Accessory output
Compressor Lead/Lag
Compressor Current Switches
Field Selectable Options
Freeze Detection Sensing Select (DI-4 and DI-5)
The freeze detection temperature sensing selection inputs 
allow the user to adjust the setpoints. The source sensors 
are wired to inputs AI-3 and AI-4 while the load sensors are 
wired to inputs AI-5 and AI-6. The setpoints for both, the 
load and source, are factory set for 33°F. In order to change 
the setpoint to 15°F on the source, remove the jumper wire 
from DI-4 (wire #56). The load setpoint can be changed by 
removing the jumper wire from DI-5 (wire #55). 
Accessory Output (DO-4)
The accessory output will be energized 90 seconds prior to 
the lead compressor output being energized. When the lead 
compressor output is turned off the accessory output will be 
deactivated after 90 seconds. The output is selectable for on 
with compressor or off with compressor operation through 
the unit mounted user interface.
°F or °C - Unit of Measure
Degrees Fahrenheit is factory set, however degrees Celsius 
can be selected using the following procedure:
To Change Unit of Measure:
• On FX10 control using up and down keys, scroll to 
“SETTINGS”
• Using up and down keys, scroll to “UNIT OF MEASURE”
hit “ENTER” and “UNIT OF MEASURE” begins flashing
• Using up and down keys, select “F” for degrees
Fahrenheit or “C” for degrees Celsius
Other Field Options
Other field selectable options are available as shown in the 
maintenance menu on page 24 of the FX10 control using a 
similar procedure as shown in the above examples. These 
would include aquastat enabling, and emergency shutdown. 
 
Control Features
Control and Safety Features
Emergency Shutdown
The emergency shutdown mode can be activated by a 
command from a facility management system or a closed 
contact on DI-2. The default state for the emergency 
shutdown data point is off. When the emergency shutdown 
mode is activated, all outputs will be turned off immediately 
and will remain off until the emergency shutdown mode is 
deactivated. The first time the compressor starts after the 
emergency shutdown mode has been deactivated, there will 
be a random start delay present.
Lockout Mode
Lockout mode can be activated by any of the following 
fault signals: refrigerant system high pressure, refrigerant 
system low pressure, heating freeze detection, cooling 
freeze detection, and compressor current sensor. When 
any valid fault signal remains continuously active for the 
length of its recognition delay, the controller will go into fault 
retry mode, which will turn off both compressors. After the 
compressor short cycle delay, the compressors will attempt 
to operate once again. If three consecutive faults occur in 60 
minutes, the unit will go into lockout mode, turning off the 
compressor(s), enabling the alarm output until the controller 
is reset. If the control faults due to the low pressure input 
being open during the pre-compressor startup check, the 
control will go into lockout mode immediately, disabling the 
compressors from starting and enabling the alarm output. 
The lockout condition can be reset by powering down the
controller, by a command from the BAS, or by the holding 
the ESC and Return keys on the user interface for 5 seconds.