Control features, Advanced freeze detection system – WaterFurnace Envision2 NXW Chiller User Manual
Page 21
 
21
ENVISION
2
NXW REVERSIBLE CHILLER INSTALLATION MANUAL
Control Features
Advanced Freeze Detection Operation:
“Pre Freeze” Alarm
Predictive freeze condition detection:
If the refrigerant temperature is within 7.2°F of the freeze 
detection setpoint, the predictive freeze detection 
algorithm is enabled, and if the logic determines that 
a freeze condition is likely to happen based on current 
conditions, the compressor of the involved refrigerant 
circuit is immediately stopped. Three (3) such events 
in 60 minutes will trigger a compressor lockout that 
requires a manual reset. In the absence of such a 
condition, the compressor is allowed to operate so that 
the refrigerant temperature may eventually be at the 
threshold of the freeze detection setpoint. NOTE: This 
Lockout produces a “Pre Freeze” detection error on 
the MUI display.
Capacity Limiting
If the leaving water temperature drops to 1.8°F above the 
freeze detection setpoint, the lead compressor is halted. 
When the leaving water temperature rises to 3.6°F above 
the freeze detection setpoint, it will be allowed to resume 
operation. This limiting is allowed to repeat indefinitely. This 
causes “COMP1 Low Limit” to be displayed on the MUI.
If the leaving water temperature drops to the freeze 
detection setpoint, the lag compressor is halted. When the 
leaving water temperature rises to 1.8°F above the freeze 
detection setpoint, it will be allowed to resume operation. 
This limiting is allowed to repeat indefinitely. This causes 
“COMP2 Low Limit” to be displayed on the MUI.
Compressor Current Switch (AI-3 EXP and AI-4 EXP)
The compressor current switch is designed to insure that 
the compressor is on when the compressor output is 
energized. This switch is normally open and closes when 
current is flowing to the compressor. If the compressor fails 
to start the switch will open. The switch must be open for a 
continuous 15 seconds for a fault to occur. After 3 faults in 
60 minutes the control will put the unit into an alarm state.
Flow Proving Switch (DI-1 and DI-10)
The load and source flow-proving switches are optional and 
can be field installed. These switches shall be normally open 
flow switches that will close when the water flow through 
the heat exchangers reach an acceptable level. The flow-
proving switches must be closed 15 seconds prior to enabling 
either compressor output (DO-1 and DO-2). If the load flow-
proving switch opens at any time both compressor outputs 
(DO-1 and DO-2) must be disabled immediately. 
High Pressure (DI-11 and DI-12)
The high-pressure switches shall be a normally closed (NC) 
switch that monitors the systems compressor discharge 
refrigerant pressures. There shall be an individual high 
pressure switch for each circuit. If the input senses the 
high-pressure switch is open during the period that the 
compressor output is enabled, it must shut down the 
compressor immediately and count the fault. The compressor 
Advanced Freeze Detection System
The source and load heat exchangers are protected by a 
multi-sourced temperature logic strategy. The temperature 
logic is based upon the refrigerant temperature sensed as 
the refrigerant is about to enter the heat exchanger; while 
entering and leaving water temperatures are being used as 
correlating factors. The detection scheme is shown as basic 
and advanced algorithms.
Basic Freeze Detection Operation: “Comp1 or 
Comp2 Freeze” Alarm
This alarm can be triggered by one of two detection 
schemes.
Hard Limit Freeze Detection
If the refrigerant temperature drops below the freeze 
detection setpoint by 1.8°F, the associated compressor 
is locked out immediately regardless of any other 
factors and requires a manual reset. NOTE: This Lockout 
produces a “Comp 1 or Comp 2 Freeze” error on the 
MUI display.
Freeze Detection
The refrigerant temperature is compared to the freeze 
detection setpoint (15°F [antifreeze] or 33°F [water] 
field selectable), and if the temperature falls below the 
setpoint for 30 continuous seconds, the associated 
compressor will be halted. This function becomes 
enabled after the first two minutes of compressor 
operation. Three such events in 60 minutes will trigger a 
compressor lockout that requires a manual reset. NOTE: 
This Lockout produces a “Comp 1 or Comp 2 Freeze” 
error on the MUI display.
In addition to the above:  
Entering Water Temperature Influence
If the entering water temperature of the evaporative 
heat exchanger is within 10°F of the freeze setpoint, 
the previously mentioned two minute delay will be 
eliminated. This allows the freeze detection to operate 
immediately when the compressor starts based on 
entering water temperature.
Leaving Water Temperature Influence
If the leaving water temperature of the evaporative 
heat exchanger is within 10°F of the freeze setpoint, the 
previously mentioned 30 second delay will begin to be 
proportionately reduced, ending at a 1 second delay 
when the leaving water temperature is 1.5°F above the 
freeze setpoint.
Dual Circuited Heat Exchanger Protection
A low temperature condition on either refrigerant circuit 
will prevent the start of both compressors. If the low 
temperature condition exists for 5 minutes when both 
compressors are off, a lockout is triggered for both 
compressors. However, if –for instance-both compressors 
are operating and circuit 1 experiences a refrigerant 
temperature below the freeze detection setpoint such 
that compressor 1 is halted, compressor 2 will not be 
halted as a result.