Compressor resistance, Thermistor resistance, Operating limits – WaterFurnace Envision2 NXW Chiller User Manual

Page 31

Advertising
background image

31

ENVISION

2

NXW REVERSIBLE CHILLER INSTALLATION MANUAL

Compressor Resistance

Model

208-230

380

460

575

120

.539 / .528 /.528

.575 / .575 / .575

2.116 / 2.088 / 2.072

3.333 / 3.289 / 3.263

180

.32 / .32 / .33

N/A

1.29 / 1.28 / 1.33

1.99 / 1.96 / 2.05

240

.33 / .33 / .33

N/A

1.13 / 1.11 / 1.10

1.73 / 1.66 / 1.75

360

.20 / .20 / .20

0.57 / 0.57 / 0.57

.83 / .83 / .83

1.32 / 1.32 / 1.32

600

N/A

.36 / .36 / .36

0.52 / .52 / .52

.82 / .82 / .82

1/30/14

Resistance values listed in ohms and measured at 25C between phases 1-2, 1-3, 2-3, respectively.
Specialized measurement device should be used for accurate resistance readings due to low resistance values.

Thermistor Resistance

Thermistor

Temperature (°F)

FX10

Resistance (Ohms)

5

746-770

14

775-803

23

808-836

32

841-869

41

875-903

50

910-938

59

946-974

68

981-1013

77

1019-1051

86

1058-1090

95

1097-1129

104

1137-1169

113

1179-1211

122

1221-1253

131

1261-1297

140

1305-1341

149

1350-1386

1/30/14

Operating Limits

Operating Limits

Cooling

Heating

(°F)

(°C)

(°F)

(°C)

Source Side Water Limits

Min. Entering Water

30

-1.1

30

-1.1

Normal Entering Water

85

29.4

60

15.6

Max. Entering Water

110

43.3

90

32.2

Load Side Water Limits

Min. Entering Water

50

10.0

60

15.6

Normal Entering Water

60

15.6

100

37.8

Max. Entering Water

90

32.2

120

48.9

Notes:

Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units

are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependant upon three
primary factors: 1) entering source temperature, 2) entering load temperature, and 3) flow rate (gpm). When any of the factors are at
the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation. Consult the
Capacity Tables for each model to determine allowable normal operating conditions. Units are not designed for outdoor installation.