Pressure Drop

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

2.4

2.6

2.8

3.0

3.2

3.4

3.6

3.8

4.0

4.2

4.4

4.6

4.8

5.0

5.2

5.4

5.6

5.8

6.0

6.2

6.4

6.6

6.8

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

220

Pressure Drop (psi)

Flow (gpm)

Water Pressure Drop vs. Flow at 30°F

Model 120

Model 180

Model 240

Model 360

Model 600

Note: Pressure drop is the same for load and source heat exchangers at 30°F fluid temperature.

Model

GPM

Pressure Drop (psi)

30°F

50°F

70°F

90°F

110°F

120

20

0.8

0.7

0.6

0.6

0.5

30

2.1

1.9

1.8

1.7

1.5

40

3.3

3.1

2.9

2.8

2.5

180

30

0.9

0.8

0.7

0.7

0.6

45

2.3

2.2

2.0

2.0

1.8

60

3.7

3.5

3.3

3.2

2.9

240

40

1.3

1.2

1.1

1.1

1.0

60

3.2

3.0

2.9

2.8

2.6

80

5.0

4.7

4.6

4.4

4.2

360

60

1.3

1.2

1.1

1.0

0.9

90

3.1

2.9

2.8

2.7

2.4

120

4.8

4.6

4.4

4.3

3.9

600

100

2.8

2.5

2.4

2.2

2.0

150

4.7

4.5

4.4

4.0

3.9

200

6.4

6.2

6.1

5.7

5.6

4/29/14