Interfaces

Operating Manual PSSu H PLC1 FS DP SN SD
1001776­EN­04

19

INFORMATION

The two data lines are also called A and B on PROFIBUS.

Always connect the A­line ("RxD/TxD­N") to the A­lines of all the other
PROFIBUS subscribers.

The B­line ("RxD/TxD­P") should only be connected to the B­lines of the
other PROFIBUS subscribers.

If communication is not established, check the connections using a continu­
ity tester.

}

Connect the connector housing to the shielding on the PROFIBUS cable. The con­
nector housing should be connected with low impedance to the mounting rail.

CAUTION!

Do not use the signals VP (+5 V ext.) and DGND (GND ext.) to supply
voltage to external devices! They are exclusively used to supply the
PROFIBUS DP bus terminating resistors.