AUTOMATIC CENTERING SENSOR ADJUSTMENT

1.

Remove the two Screws located on the front panel of the
AE120 (See Figure 16).

2.

Slide the AE120 chassis out of the housing.

3.

Set the AE120 Power Switch to ON and set the Mode
Switch to MAN (See Figure 16).

4.

Connect a voltmeter across Terminals 9 and 10 of the
AE120 (See Figure 17).

5.

Using the Manual Push Buttons, center the Roll Base
and verify the edges of the Roll Base and Base are
parallel to each other (See Figures 16 and 18).

6.

Loosen the Socket Head Cap Screws and adjust the
Proximity Sensor Bracket as necessary to obtain a 7.0
volt reading on the voltmeter (See Figure 18); then,
tighten the Socket Head Cap Screws when the adjustment
is complete.

7.

Disconnect the voltmeter from Terminals 9 and 10.

8.

Set the Mode Switch to CENTER (See Figure 16) and
adjust the C. ZERO pot to maintain the Web Guide at its
neutral position (See Figure 19).

9.

If the Web Guide hunts or oscillates back and forth with
the Mode Switch set to CENTER, adjust the C. GAIN pot
until the motion stops (See Figure 19).

FIGURE 16

BR

Extension

Retraction

BL

GN

WH

RD

BK

GN

WH

RD

BK

Power Supply

AC100V~240V

50/60 Hz100VA

Motor

Actuator

Limit

Switch

Auto

Centering

Sensor

Left

Sensor

Right

Sensor

1

M

2 3

4 5

6

7 8

9 10

11 12 13 14 15 16

17

18

FIGURER 17

FIGURE 18

FIGURE 19

MODEL
AE120

MAN

CENTER

AUTO

AUTO

POWER

ON

LEFT

CPC

RIGHT

MAN

Remove

Screw

Remove

Screw

Power

Switch

Manual Push

Buttons

Mode

Switch

Proximity

Sensor

Bracket

Roll Base and Base

must be parallel.

Socket Head

Cap Screws

LAMP

PH B1

GAIN 1

PH B2

GAIN 2

OUTPUT

F. ADJ

C. ZERO C. GAIN

C. ZERO

C. GAIN

Advertising