Storing the ups and batteries, When to replace batteries – Dell H967N User Manual

Page 61

Advertising
background image

61

UPS Maintenance

|

6

Close the metal battery cover.

Adjust the battery connector so that the door closes properly. Push the door slightly to the right
and then to left.

7

Tighten the thumbscrew.

Torque the screw to 0.7 Nm (6.2 lb in).

8

Replace the UPS front cover (see Figure 26).

Figure 26. Replacing the UPS Front Cover

Storing the UPS and Batteries

If you store the UPS for a long period, recharge the battery every 6 months by plugging the UPS into a
power outlet. The batteries charge to 90% capacity in approximately 4 hours. However, it is
recommended that the batteries charge for 48 hours after long-term storage.

Check the battery recharge date on the shipping carton label. If the date has passed and the batteries
were never recharged, do not use the UPS. Contact your service representative.

When to Replace Batteries

When the status summary screen displays the UPS fault icon with the “Service Battery” alarm and the
audible alarm sounds continuously, the batteries may need replacing. Contact your service
representative to order new batteries.

NOTE:

With the user-replaceable battery feature, UPS batteries can be replaced easily without turning the UPS

off or disconnecting the load.