Register map of the dhb-3xx meter – CIRCUTOR DHB Series User Manual
Page 28

28
Table 4
Range
of addresses
Value type
Description
4000-4100
integer (16 bitów)
Value placed in a 16-bit register.
7000-7199
float (32 bity)
Value placed in two successive
16-bit registers. Registers include
the same data as 32-bit register
from the area 7500. Registers are
only for readout.
7200-7400
float (32 bity)
Value placed in two successive
16-bit registers. Registers include
the same data as 32-bit register
from the area 7600. Registers can
be read out and written.
7500-7599
float (32 bity)
Value placed in a 32-bit register.
Registers are only for readout.
7600-7700
float (32 bity)
Value placed in a 32-bit register.
Registers can be read out and
written.
6.3. Register Map of the DHB-3xx Meter
Code
Meaning
03
Readout of n-registers
06
Readout of single register
16
Write of n-registers
17
Identification of the slave device.
Following functions of the MODBUS protocol hale been implemented
in the DHB-3xx meter:
Table 3