CIRCUTOR DHB Series User Manual
Page 36

36
Type of analog output
4030
tYP_A
w/r
0...2
Value
0
Voltage 0...10 V
1
Current 0...20 mA
2
Current 4...20 mA
Baud rate
4031
bAUd
w/r
0...3
Value
0
4800 bit/s
1
9600 bit/s
2
19200 bit/s
3
38400 bit/s
Baud rate
4032
Prot
w/r
0...3
Value
0
RTU 8N2
1
RTU 8E1
2
RTU 8O1
3
RTU 8N1
Device address
4033
Addr
w/r
0...247
Update display parameters
4034
sAvE
w/r
0...1
Value
0
without changes
1 update
Write of standard parameters
4035
SEt
w/r
0...1
Value
0
without changes
1
set standard parameters
Password for parameters
4036
SEC
w/r
0...60000
Value
0
without password
1...60000 entry in parameters preceded by a
request about the password
Current time
4037
HoUr
w/r
0...2359
This parameter occurs in the ggmm format, where:
gg - means hours,
mm – means minutek.
The introduction o a wrong hour will cause the set-
ting 23, however the introduction of wrong minutes