Instruction Manual

12

Keep the capacitor terminals and reactors clean.

Verify the state of the contactors of operating elements.

Check that the capacitor current is not less than 25% or greater than 120% of the nominal
value by phase and that there is no phase unbalance greater than 15%.

Annually

Perform dielectric rigidity tests on the different elements of the power circuit, applying 2.5 kV
during 1s between the capacitor and earth terminals.

Check the capacity of the different steps. An indirect verification can be performed by checking
that the consumption matches the value stated in Table 7.5, with a maximum deviation of ±
10%.

Check the tightness of all terminal connections on the different power elements.

Inspection of the fuses.
-

Power circuit: NH fuses. Check continuity and temperature.

-

Control Circuit protection: Neozed fuses or circuit breaker. Check continuity and
temperature.

7.2.2 Tightening the electrical connections.

The connections must be tight. The following tightening torques for the fuse bases and
contactors are listed in tables 7-1 and 7-2

Table 7-1.- Tightening torques of the cables to the fuse bases

FUSE BASE

TORQUE (Nm)

NEOZED 63 A

3.6

NH-00

15.2