Table 7-5.- Nominal consumption of the LC steps of an FR filter, depending on its power

CURRENT

POWER

230V

400V

In

In

2.5 kvar

6.28 A

3.6 A

5 kvar

12.56 A

7.2 A

7.5 kvar

18.85 A

10.8 A

10 kvar

25.12 A

14.4 A

12.5 kvar

31.41 A

18 A

15 kvar

37.7 A

21.6 A

20 kvar

50.24 A

28.8 A

25 kvar

62.82 A

36 A

30 kvar

75.4 A

43.2 A

40 kvar

100.48 A

57.6 A

50 kvar

125.64 A

72 A

60 kvar

150.8 A

86.4 A

70 kvar

175.92 A

101.1 A

80 kvar

200.96 A

115 A

- Check the voltage on all of the reactor's windings (input to output of the same winding, not

between phases). The voltage depends on the filter's p% factor (see label on the
equipment). The voltage must be in accordance with the following formula:

%)

p

100

(

%

p

.

577

,

0

V

V

)

phase

_

to

_

phase

(

Mains

L

−

=

For example, in the case of the 400V grid and p%=7, V

L

=17.38V. For the 400V grid and

p%=14, V

L

=37.57V. The value is proportional to the voltage for other voltages.

NOTES:

•

When the consumption of the steps is 25% less than that stated in Table 7-5 and the voltage
is within the tolerance limits, this is a sign of degradation of the capacitors. These must be
replaced with a suitable spare part if these symptoms are detected in a step.

•

When the consumption of the steps is 10% more than the values stated in Table 7-5, this can
be caused by the presence of resonances. If this is detected, measure the grid's voltage THD
(it must be under 5%) or check the filter's tuning frequency.

•

If the voltage drop in a reactor deviates from the values stated in this section, check the
reactor. This phenomenon can be caused by the presence of a resonance.

7.3.3

PF Regulator Checkings.

Refer to the manual of the specific PF regulator used in the filter bank. This
manual is always supplied with the filter bank.

•

Make sure that there are no damaged segments on the display (abnormal brightness).

•

Make sure that regulator's keyboard is working properly:

- Enter Setup and check the adjusted values
- Force the manual connection and disconnection of a step.

7.4

Environmental Conditions:

•

Check that the maximum environmental conditions listed in section 4.3 are observed