Fig. 3-2 .-Unloading with a Forklift

3.3

Storage

The following storage recommendations should be followed for capacitor banks with detuned
filters:

-

Avoid placing it on uneven surfaces.

-

Do not store in outdoor areas, humid areas or areas exposed to the splashing of water.

-

Avoid hot spots (maximum environmental temperature: 45 ºC)

-

Avoid saline and corrosive environments.

-

Avoid storing the equipment in areas where a lot of dust is generated or where the risk of
chemical or other types of contamination is present.

-

Do not place any weight on top of the equipment cabinets.

4

TECHNICAL FEATURES

4.1

Label with the equipment's features

The label with the equipment's features is located inside it, generally next to the PF regulator (refer
to Fig. 4-1). The filter bank includes the p% information, which states the filter's tuning factor. This
information is important to establish the filter's resonance frequency.

Ref.

Cod.

Nr Serie

Q

N

(U

max

)

p% filtro

Norma/Prot

U

N

/U

max

/f

N

I

max

U

aux

/ f

N

Temp

I

cc

FR8-600-440

R36625

3094701005

600 kvar

50 + 50 + 5x100 kvar

7%

EN-61921, EN-61642 / IP21

3x400 V/440 V/50 Hz

750 A

230 V/50Hz

-25 / +45 ºC

35 kA

Made in UE / Spain

Type

Code

Serial Nr

Reactive Power at Umax

Nr of Steps

p% overvoltage factor, U

L

/U

C

in %

Standards / Protection degree

Rated & Maximun voltage / Rated frequency

Maximum current

Auxiliary control voltage (1)

Range of allowable temperature inside the cabinet

Default value. See particular values in the label

80 mm

1

0

0

m

m

Fig. 4-1.- Label showing the main characteristics

4.2

Electrical features

-

Operating voltage and nominal frequency: U

n

/ f , listed on the label

-

Design voltage:

U

n

+ 10% (440 V for 400V equipment)

-

Nominal power and distribution of steps:

Q

n

and composition, (see label)

-

Overvoltage factor, p%

Standard 7% ,

Others 14%, 8.2% and 5.67% (see label)

-

Total loss:

Standard 3.5 to 4 W/kvar

-

Residual discharge voltage:

75 V after 3 minutes

-

Overload capacity:

1,3 . I

n

in all items

-

Auxiliary control voltage:

U

aux

, listed on the label.

NOTE: In general, use a 1.5 mm

2

cable to supply external power.

If “Internal” , is marked, the equipment does not require external power.