7 PERIODICAL SERVICING.

Maintenance should be carried out in accordance to the safety procedures detailed in section 8.
LCL filters require minimal maintenance, but it is recommended that the following procedures be
undertaken:

During the first month of operation.

Visually inspect the capacitors.

Examine the protective fuses.

Control the temperature.

Control the service voltage (especially under low load conditions).

Retighten terminals and connections.


Annually.

Check the capacitor's nominal current.

Clean the terminals and isolators on the capacitors.

Check that the terminal connections are tightened.

Check the condition of the contacts on the contactor if there is overcompensation protection.

8 SAFETY.

Before handling any device in the filter disconnect the supply upstream. The filter does not have any
main switch. Switch must be placed at the line head.

Even when the bank is disconnected, there still may be voltage in the capacitors. Therefore, after
having removed the supply voltage, wait for 3 minutes and then short circuit them and earth the
terminals or output cables on each capacitor.


9 TECHNICAL SERVICE AND GUARANTEE.

CIRCUTOR guarantees its products against manufacturing faults for one year from the date of
delivery. The guarantee does not cover protective devices (fuses) nor operating devices subject to
natural wear and tear.

This guarantee becomes void in the event of improper handling or disregard of the handling
conditions.

CIRCUTOR has its CONSULTANCY AND TECHNICAL ASSISTANCE service at your disposal.