4


WARNING!!!: Due to the LCL filter performance mode, it is quite likely to find elevate harmonic
distortion levels of voltage at the input of the speed drive (downstream to the filter output reactor (L2)).
This voltage distortion should cause no malfunction of the speed drive to be filtered, but it is very much
recommendable, in case that this power drive is taken the auxiliary voltage supply of the control
system from the input of the drive, to take this auxiliary supply from the LCL input, that is, upstream to
the filter input reactor (L1).

Fig. 2.a. Mains supply without LCL filter

Fig. 2.b. Mains supply without LCL filter

4 TECHNICAL CHARACTERISTICS

4.1 General.

Standard voltage (phase to phase) 400V (Others on request)
Frequency

50Hz for types LCL-35-xx or 60 Hz for types LCL-36-xx

Rated load current

See table of types

Rated filtering current

See table of types

Parallel filter protection

Fuses NH or NZ type depending on size

Residual THD

Aprox. 8%

Voltage drop at rated current

< 2%

Standards

EN 60439, EN 60831 ; EN-50081-1, EN-50081-2 , class A

Ambient temperature

Ambient : 40ºC

Relative Humidity

80%

4.2 Reactors

Core / Coil

High permeability metal sheet / Aluminium

Isolation voltage

2kV

Tolerance in L value

<3%

Saturation

L=5%

1,6 of rated current

Maximum ambient temperature

60ºC

Internal temperature at Irated

<110ºC

Protection thermostat trip

90 ºC

Total maximum overload

(n.In)2

25%

Permanent

20%

Transient (1 min)

2 Irated

4.3 Capacitors

Dielectric

Polypropylene Self-healing