7.10. GENERAL I/O

General I/O provide analog input as well as digital output. Each General I/O port can be used either as input or
as output.

General I/Os are applicable as follows

GENERAL I/O 1 - 8 on ipCUE-alpha, ipCUE-gamma, ipCUE-delta, ipCUE-epsilon, ipCUE-sigma

and not applicable for ipCUE-beta.

Pull-up resistor 680 ohms is connected to +5 VDC and can be switched on and off for each I/O independently.
I/O voltage with pull-up on is approx. +4.3 VDC, because protection diode is connected in series (0.7 V drop-
down).

Analog input is rated

0 – 5 VDC for ipCUE-alpha, ipCUE-gamma, ipCUE-delta, ipCUE-epsilon

0 – 20 VDC for ipCUE-sigma.

Analog to digital (A/D) converter has 10-bits precision (i.e. 1024 levels). Digital output can switch max. 24
VDC / 80 mA. Output voltage for output switch on is approx. 0.6 V.

IO schematic diagram

Connector pin out for ipCUE-alpha, ipCUE-gamma, ipCUE-delta, ipCUE-epsilon

Note: All pins labeled G are connected together.

Connector pin out for ipCUE-sigma

User Manual ipCUE Controllers

www.cuesystem.com

Page 25 of 52

GENERAL I/O on ipCUE controller

INPUT 1 – 8

OUTPUT 1 – 8
value CLOSE / OPEN

680 Ohm

PULLUP 1 – 8
value ON / OFF

ON OFF

+5 VDC

A

D

10 bit

Input / Output

Ground

Pin

G

S

GENERAL I /O

2-pin 3.5 mm