Installation – Desa VML27PR User Manual

Page 10

Advertising
background image

www.desatech.com

111115-01F

10

inStALLAtion

Continued

Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note:

If using a mantel, proceed to If Using

Mantel. If not using a mantel, follow the informa-

tion below.

You must have noncombustible material(s) above

both fireplace openings. Noncombustible materials

(such as slate, marble, tile, etc.) must be at least

1/2" thick. With sheet metal, you must have non-

combustible material behind it. Noncombustible

material must extend at least 8" up (for all models).

If noncombustible material is less than 12", you

must install the fireplace hood accessory. See

Figure 5 at right for minimum clearances.
IMPORTANT:

If you cannot meet these minimum

clearances, you must operate heater with chimney

flue damper open. Go to Installing Damper Clamp

Accessory for Vented Operation, page 12.
If Using Mantel
You must have noncombustible material(s) above

the fireplace opening. Noncombustible materials

(such as slate, marble, tile, etc.) must be at least

1/2" thick. With sheet metal, you must have non-

combustible material behind it. Noncombustible

material must extend at least 8" up (for all models).

If noncombustible material is less than 12", you

must install the fireplace hood accessory. Even if

noncombustible material is more than 12", you

may need the hood accessory to deflect heat away

from your mantel shelf. See Figure 5 and 6 and

Figure 7, page 9, for minimum clearances.
IMPORTANT:

If you cannot meet these minimum

clearances, you must operate heater with chimney

flue damper open. Go to Installing Damper Clamp

Accessory for Vented Operation, page 12.

Figure 5 - Heat Resistant Material (Slate,

Marble, Tile, etc.) Above Fireplace

Noncombustible
Material

Requirements for

Distance (A)

Safe Installation

1" or more

Noncombustible

material OK.

Between 8"

Install fireplace hood

and 1"

accessory (GA6050,

GA605 or GA6053, see

Accessories, page 9).

Less than 8"

Noncombustible

material must be

extended to at least 8".

See Between 8" and 1",

above. If you cannot

extend material, you must

operate heater with flue

damper open.

MANTEL CLEARANCES

In addition to meeting noncombustible material

clearances, you must also meet required clearances

between fireplace openings and mantel shelf on

each side of the fireplace. If you do not meet the

clearances listed below, you will need a hood.
Determining Minimum Mantel Clearance

If you meet minimum clearance between mantel

shelf and top of fireplace opening, a hood is not

required (see Figure 6, page 11).
Determining Minimum Mantel Clearance
When using a Hood

If minimum clearances in Figure 6, page 11 are not

met, you must have a hood. When using a hood

there are still certain minimum mantel clearances

required. Follow minimum clearances shown in

Figure 7, page 11 when using hood.

Advertising