WARNING: Use pipe joint

sealant that is resistant to liquid

petroleum (LP) gas.

We recommend that you install a sediment trap in

supply line as shown in Figure 18. Locate sediment

trap where it is within reach for cleaning. Install

in piping system between fuel supply and heater.

Locate sediment trap where trapped matter is not

likely to freeze. A sediment trap traps moisture and

contaminants. This keeps them from going into

heater controls. If sediment trap is not installed or

is installed wrong, heater may not run properly.

CAUTION: Avoid damage to

gas control. Hold gas control

with wrench when connecting it

to gas piping and/or fittings.

inStALLAtion

Continued

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an

open flame to check for a leak.

Apply a noncorrosive leak detec-

tion fluid to all joints. Bubbles

forming show a leak. Correct all

leaks at once.

CAUTION: Make sure exter-

nal regulator has been installed

between propane/LP supply

and heater. See guidelines un-

der Connecting to Gas Supply,

page 14.

pRESSURE TESTING GAS SUppLY
pIpING SYSTEM
Test pressures In Excess Of 1/2 pSIG
(3.5 kPa)

1. Disconnect appliance with its appliance main

gas valve (control valve) and equipment

shutoff valve from gas supply piping system.

Pressures in excess of 1/2 psig will damage

heater regulator.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

4. Check all joints of gas supply piping system.

Apply noncorrosive leak detection fluid to all

joints. Bubbles forming show a leak.

5. Correct all leaks at once.

6. Reconnect heater and equipment shutoff

valve to gas supply. Check reconnected fit-

tings for leaks.

* Purchase the optional CSA design-certified

equipment shutoff valve from your dealer. See

Accessories, page 29.

** Minimum inlet pressure for purpose of input

adjustment.

Figure 18 - Gas Connection

Gas Control

3" Minimum

CSA Design-
Certified
Equipment Shutoff
Valve With 1/8"
NPT Tap*

Approved
Flexible Gas
Hose (if allowed
by local codes)

Cap Pipe Tee
Nipple Joint

Sediment Trap

Natural Gas

From Gas Meter

(5" W.C.** to 10.5"

W.C. Pressure)

Propane/LP Gas

From External

Regulator

(11" W.C.** to

14" W.C.

Pressure)