Load considerations, Inductive loads, Outline drawings – AMETEK SFA Series User Manual

Page 32: Onsiderations, Inductive loads -8, Utline, Rawings, Table 2–6 maximum ac current ratings -8, Table 2–7 recommended lugs -8, Table 2–8. recommended sense connector tools -8

Advertising
background image

Installation

Sorensen SFA Series

Refer to Table 2–6 for AC input current requirements and Section 1.2.3 for
output current requirements.

Input Line Current

Input V

5 kW

10 kW

15 kW

20 kW

25 kW

30kW

Unit of

Measure

200-240VAC

21 41 62 83 103

124

340-440VAC

14

27 40 54 67 80

480VAC 13 26 39 52 65 78

Amps AC

per phase

Table 2–6 Maximum AC Current Ratings

Refer to Table 2–7 for input/output lug recommendations.

Lug Manufacturer

3U Models Input/Output

6U Models Input/Output

Panduit

“PN” Series or equivalent

“LCA” Series or equivalent

Table 2–7 Recommended Lugs

The recommended tools for installation and extraction of the sense connector
are listed next, in Table 2–8.

Tool

Manufacturer

Manufacturer P/N

Crimping Device

Molex

11-01-0197

Extracting Device

Molex

11-03-0044

Table 2–8. Recommended Sense Connector Tools

2.6

LOAD CONSIDERATIONS

2.6.1

I

NDUCTIVE

L

OADS

To prevent damage to the power supply from inductive loads, the SFA has
incorporated a overvoltage shutdown circuit on the output. The overvoltage is
preset for approximately 110% of the total rated output voltage. If the output
voltage exceeds this amount for more than a few milliseconds, the output will
shutdown. In order to reset the unit, the input standby switch, will need to be
cycled on and off.

2.7

OUTLINE DRAWINGS

Figure 2-1 and Figure 2–2, next, show the outlines and overall dimensions of
the 3U and 6U models of the SFA Series product line.

2-8

M550292-01 Rev G