Figure 2-2, Shelf airflow, Site preparation – Artesyn Centellis 4410 (AXP-1410) Installation and Use (July 2014) User Manual
Page 71
Advertising

Site Preparation
AXP 1410 Installation and Use (6806800H70L)
71
Fan trays are mounted in the shelf top. The figure below shows the general airflow for the
system.
The Cooling subsystem is compliant to CP-TA B.4. The cooling system provides for greater than
40 CFM for the front blade and 5.0 CFM for the RTM.
The actual cooling performance depends on the slot population and the heat sink design of
installed blades and should be validated based on the used system configuration.
The cooling subsystem is designed to provide 31.1 CFM in the front and presence of any single
cooling failure.
Figure 2-2
Shelf Airflow
RTM
Outlet Plenum
Chassis
Front
Chassis
Rear
Chassis
Exhaust
Air Flow
Lower Front Air Intake
Lower FTMs
Upper FTM
Room
Ambient
Air Flow
PEM
Exhaust
Advertising
This manual is related to the following products: