2 power cable termination, Figure 3-2, Dc power connection detail – Artesyn Centellis 4410 (AXP-1410) Installation and Use (July 2014) User Manual
Page 81: System installation
Advertising

System Installation
AXP 1410 Installation and Use (6806800H70L)
81
3.3.2.2
Power Cable Termination
Custom lugs are used with large gauge wires for up to 80 AMPs DC (4 AWG) when connecting
to the PEM. These are shipped with the product.The lugs are angled to allow the cables to be
dressed below the cable management tray, thus protecting the circuit breakers from
accidental tripping.
Figure 3-2
DC Power Connection Detail
OFF
ON
OFF
ON
-48 VDC RTN
-48 VDC
VDC RTN
-48 VDC