Installation
(for qualified installers only)
15
Travis Industries
4140611
100-01385
Minimum Framing Dimensions - Rear Vent Configuration
Route the
electrical line to
a position to the
left rear of the
fireplace.
Vent Clearances 8" (203mm) dia. Vent:
1" (25mm) to the sides, 1" (25mm)
below, and 3" (76mm) above the vent to
combustibles.
Included Firestop (required)
Part # 93006094
Center of Rear Vent
30-3/4"
781mm
38"
965mm
41-1/4"
1048mm
38-1/2"
978mm
20-3/4"
528mm
HINT: place the fireplace so the center
line is at least 5" (127mm) from both
vertical framing members at the rear (this
allows the vent to pass through the
framing without modfications)
25-3/4"
654mm
Minimum enclosure height = 38-1/2" (978mm)