44 installation, Mantel requirements, For qualified installers only) – Avalon Firestyles 864 TRV GS2 Installation User Manual
Page 44: Combustible mantels, Non-combustible mantels

44 Installation
(for qualified installers only)
Travis Industries
4140611
100-01385
Mantel Requirements
Combustible Mantels
Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured
from the face of the fireplace) must fall in the shaded portion of the table.
Any material that protrudes more than 3/4” (19mm) from the non-combustible facing is considered a
mantel and must meet the mantel requirements.
Examples:
- If you wish to have an 8” (203mm) deep mantel, it must be at least 8” (203mm) above the fireplace face (44-3/4”, 1137mm above the base).
- If you wish to have a mantel 6” (152mm) above the fireplace face, it must be no deeper than 6” (152mm).
Non-Combustible Mantels
Non-combustible mantels must meet the clearances listed for combustible mantels. However, if you do
wish to reduce the clearances by using a non-combustible mantel, the following requirements must be met:
Non-combustible
mantel and facing
must extend from the
top of the appliance to
the top surface of the
mantel.
A
non-combustible
header must be used
(metal stud).
36-3/4"
933mm
a
b
Base of the Fireplace
Combustible mantel columns (legs) that protrude
more than 3/4" (.75mm) from the glass frame must
meet the sidewall clearance. If they protrude 3/4"
(.75mm) or less, they must meet the facing
clearance, 2-1/4" (57mm) from the glass frame - to
the side of the fireplace, not in front of it.
Non-combustible mantel columns do not have a
minimum clearance.
Combustible Mantel
Maximum Mantel Depth (b)
Mantel
Height
Above
Face (a)
0mm (0")
25mm (1")
51mm (2")
203mm (8")
178mm (7")
152mm (6")
127mm (5")
102mm (4")
76mm (3")
229mm (9")
254mm (10")
279mm (11")
305mm (12")
330mm (13")
356mm (14+")
0mm (0")
25mm (1")
51mm (2")
203mm (8")
178mm (7")
152mm (6")
127mm (5")
102mm (4")
76mm (3")
229mm (9")
254mm (10")
279mm (11")
305mm (12")
SIDE OF FIREPLACE
Drywall
Non-Combustible Mantel
Non-Combustible Framing (metal studs)
must be used for the header.
Non-Combustible Facing