Basler Electric DGC-2020HD User Manual
Page 165
Advertising

9469300990 Rev B
155
Table 47. Settings for Configurable Protection
Locator
Setting
Range
Increment
Unit
A
Label Text
Up to 16
alphanumeric
characters
n/a
n/a
B
Parameter Selection
∗
n/a
n/a
C
Arming Delay
0 to 300
1
seconds
D
Hysteresis
0 to 100
0.1
%
E
Alternate Frequency Scale
Factor
0.001 to 100
0.001
n/a
F
Voltage Low Line Scale Factor
0.001 to 3
0.001
n/a
G
Current Low Line Scale Factor
0.001 to 3
0.001
n/a
H
Mode
Disabled, Over, or
Under
n/a
n/a
I
Threshold
–999,999 to 999,999
0.01
n/a
J
Activation Delay
0 to 300
1
seconds
K
Alarm Configuration
Status Only, Pre-
Alarm, or Alarm
n/a
n/a
∗See Parameter Selection, above, for a complete listing of selectable parameters.
DGC-2020HD
Configurable Protection
Advertising