Basler Electric DGC-2020HD User Manual
Page 324
Advertising
314
9469300990 Rev B
AEM-2020
DGC-2020HD
Figure 196. Settings Explorer, Programmable Inputs, Remote Analog Inputs, AEM 1 Input #1
Table 87. Settings for AEM x Input #y
Locator
Setting
Range
Increment
Unit
A
Label Text
n/a
n/a
n/a
B
Hysteresis
0 to 100
0.1
%
C
Input Type
Voltage or Current
n/a
n/a
D
Arming Delay
0 to 300
1
seconds
E
Out of Range Alarm Type
Status Only, Pre-
Alarm, or Alarm
n/a
n/a
F
Param Min
-999,999 to 999,999
varies
n/a
G
Param Max
-999,999 to 999,999
varies
n/a
H
Min Input Current
4 to 20
0.1
milliamps
I
Max Input Current
4 to 20
0.1
milliamps
J
Min Input Voltage
0 to 10
0.1
volts
K
Max Input Voltage
0 to 10
0.1
volts
L
Mode
Disabled, Over, or
Under
n/a
n/a
M
Threshold
-999,999 to 999,999
0.01
n/a