Expansion Module Connections (CAN 1)

The AEM-2020 (Analog Expansion Module) and CEM-2020 (Contact Expansion Module) are optional
modules that may be installed with the DGC-2020HD. These modules interface to the DGC-2020HD via
the “CAN 1” interface, thus the CAN terminals (51, 52, and 53) are the only common connections
between the DGC-2020HD, AEM-2020, and CEM-2020. Up to four CEM-2020 modules and up to four
AEM-2020 modules are supported on a network. Typical connections are illustrated in Figure 13.

Refer to the AEM-2020 and CEM-2020 chapters for more information.

Figure 13. DGC-2020HD Expansion Module CAN Connections

Installation for CE Systems

For CE compliant systems, it may be required to route ac voltage and current sensing wires separately
from other wires.

P0071-52

DGC-2020HD

53) SHIELD

52) CAN 1 H

51) CAN 1 L

AEM-2020 (2)

GND

CANH

CANL

CEM-2020 (1)

GND

CANH

CANL

CEM-2020 (2)

GND

CANH

CANL

CEM-2020 (3)

GND

CANH

CANL

CEM-2020 (4)

GND

CANH

CANL

AEM-2020 (1)

GND

CANH

CANL

AEM-2020 (3)

GND

CANH

CANL

AEM-2020 (4)

GND

CANH

CANL