Basic information

11

BK 7000


Electrical data

The electrical data specific to the fieldbus is given in this chapter. The fol-
lowing table lists an overview of all data:

Technical data

BK7000

Voltage supply

24 V DC (20 V...29 V DC)

Input current

70 mA + (total K-Bus current)/4
500 mA max.

Starting current

2.5 x continuos current

Output current K bus

1750 mA max.

Configuration possibility

by KS2000 or the controller

Number of bus terminals

64

Digital peripheral signals

256 inputs/outputs

Analog peripheral signals

256 inputs/outputs

Peripheral bytes

512 bytes I and 512 bytes O

Bus connection

Two BNC-connectors (ControlNet A and B) and 1 NAP-Port

Baud rates

5 MBaud (ControlNet V1.5)

Voltage power contact

24V DC / AC max.

Current load power con.

10 A max.

Max. voltage capacity

500 Veff (power contact / supply voltage/field bus)

Weight approx.

170g

Operating temperature

0°C ... +55°C

Storage temperature

-20°C ... +85°C

Relative humidity

95% non-condensing

Vibration /shock resistance

conforms to IEC 68-2-6 / IEC 68-2-27

EMC resistance burst / ESD

conforms to EN 50082 (ESD,Burst) / EN50081

Orientation for mounting

Any

Type of fuse

IP20


Current consumption on the
K-Bus

For operation of the K-bus electronics, the bus terminals require energy
from the K-bus that is supplied by the bus coupler. Refer to the catalog or
the corresponding data sheets of the bus terminals for details of the K-bus
current consumption. In doing so, pay attention to the maximum output
current of the bus coupler that is available for powering the bus terminals.
Using a special power supply terminal (KL9400), power can be fed back
into the K-bus at any chosen point. If you wish to use a power supply ter-
minal, please contact Beckhoff’s technical support. .