BECKHOFF BK7000 User Manual

Page 16

Advertising
background image

Basic information

15

BK 7000

If a fault occurs during normal operation, the error code will not be output
on the LEDs until the bus coupler has been requested to diagnose the bus
terminals. This diagnostic request is generated after the equipment is
switched on.

Fieldbus errors

The fieldbus status LEDs A and B indicate the current ControlNet bus
status of the corresponding channel. The other two LEDs are reserved for
the future.

Priority

indicator state

how to view

cause

Highest

(1)

both steady off

viewed together

reset or no power

2

both steady red

viewed together

failed link interface

3

alternating red /
green

viewed together

self test

4

alternating red /
off

viewed together

bad node configuration (such as duplicate MAC ID)

5

steady off

viewed independently

channel disabled or channel not supported

6

flashing red /
green

viewed independently

invalid link configuration

7

flashing red / off

viewed independently

link fault or no MAC frames received

8

flashing green /
off

viewed independently

temporary channel error, or listen-only

Lowest

(9)

steady green

viewed independently

normal operation


Please note that there is an association between the green I/O LED and
the fieldbus. The I/O LED lights up when access is made to the internal K
bus. The green I/O LED is not lit until data begins to be exchanged via the
fieldbus.

The bus coupler does, however, interrogate the configuration of the bus
terminals after power on and does not exchange any data with the termi-
nals. That is to say, the red I/O LED goes off after an error-free start up
without the green I/O LED having to light up. Then, the green I/O LED does
not light up until data transfer is begun via the field bus.

If a terminal bus error occurs during operation, the procedure followed con-
forms to the reaction to the terminal bus errors parameterisation. If the
terminal bus error already occurs during start up, the slave does not assu-
me ControlNet data transfer.


Advertising