ControlNet coupler BK7000 in the ControlNet

19

BK 7000


To set up this connection, the following parameters of the FwdOpen-
service have to be adjusted:

Net O->T connection

parameters

network connection type

Multicast

fixed/variable

Fixed

priority

Scheduled priority

size

No of bytes (word-aligned) of the terminal bus output
data (depending on the calculating rules for terminal
bus input and output data) + 4 bytes scanner status +
2 bytes transport header

Net T->O connection

parameters

network connection type

Point-To-Point

fixed/variable

Fixed

priority

Scheduled priority

size

No of bytes (word-aligned) of the terminal bus input
data (depending on the calculating rules for terminal
bus input and output data) + 4 bytes adapter status + 2
bytes transport header

Transport class /

trigger

client / server

Client

transport type

Cyclic

transport class

Class 1

Connection path

class

0x04

connection point inputs

0x00

connection point outputs

0x00

electronic key, vendor ID

0x006C

electronic key, product ty-
pe

0x0080

electronic key, product co-
de

0x1B58