Save the configuration, Configuration with rs networx 1.03 – BECKHOFF BK7000 User Manual

Page 24

Advertising
background image

ControlNet coupler BK7000 in the ControlNet

23

BK 7000

Set the input and output data size for the BK7000 according to the connec-
ted terminals and the desired mapping. Set the config size to 0 for default
settings or 4 for custom settings.


Save the configuration


Configuration with RS Networx 1.03

With RS Networx 1.03 the BK7000 in standard will not be supported. The
BK7000 can be configured like an 1771 ACN®15-I/O-adapter from Allen-
Bradley. Instead of the assembly object the BK7000 in 1771-Mode sup-
ports two objects: the rack object for digital terminals and the 1771-generic
module for anlog terminals.

The input and output size of the digital object must be the number of words
of the digital inputs/outputs.

The input and output size of the analog object must be the number of
words of the analog inputs/outputs. The same rules as for the assembly
object will be used for the analog object.

For the digital object insert a discrete rack in the ControlNet configuration,
for the analog object insert a module and select the „1771-Generic“-
module.

The config size in the 1771-Mode must be zero.