Technical data – BECKHOFF KL3201 User Manual

Page 5

Advertising
background image

Technical data

KL3201, KL3202 and KL3204

3


Technical data

Technical data

KL3201

KL3202

KL3204

Number of inputs

1

2

4

Power supply

via the K-Bus

Sensor types

PT100, PT200, PT500, PT1000, Ni100, Ni120. Ni1000 resistance
measurement (e.g. potentiometer connection)

Connection

2 or 3-wire (pre-set to 3-wire)

2 wire

Temperature range

-200°C ... +850°C (PT sensors); -60°C ... +250°C (Ni sensors)

Resolution

0.1°C per digit (measuring range 10 to 5000 Ω: 0.5°C per digit)

Electrical isolation

500 V (K-Bus/signal voltage)

Conversion time

~ 200 ms

~ 250 ms

Measuring current

typically 0.5 mA

Meas. error (total meas. range)

< ± 1°C

< ± 1 C (at 0°C ... +55°C)
< ± 1.5 C (at utilization of the extended
temperature range)

Bits width in process image

Input: 1 x 16 bits of
data
(1 x 8 bit
control/status
optional)

Input: 2 x 16 bits of
data
(2 x 8 bit
control/status
optional)

Input: 4 x 16 bits of
data
(4 x 8 bit
control/status
optional)

Current consumption from K-Bus

typically 60 mA

Configuration

no address setting, configuration via bus coupler or controller

Special features

open-circuit recognition

Weight

approx. 70 g

Operating temperature

0°C ... +55°C

-25°C ... +60°C in operation (extended
temperature range)
0°C ... +55°C (according to cULus for
Canada and USA)
0°C ... +55°C (according to ATEX, see
special conditions)

Storage temperature

-25°C ... +85°C

-40°C... +85°C

Relative humidity

95 % no condensation

Vibration / shock resistance

according to EN 60068-2-6 / EN 60068-2-27

EMC resistance burst / ESD

according to EN 61000-6-2 / EN 61000-6-4

Installation position

variable

Protection class

IP20

Approvals

CE, cULus, ATEX