Technical data – BECKHOFF KL6001 User Manual

Page 5

Advertising
background image

Technical data

KL6001

5


Technical data





Technical data

KL6001

Data transfer channel

2 (1/1), TxD and RxD, full duplex

Data transfer rate

9600 Baud (8N1) default, (max. 19200 Baud)

Bit distortion

< 3%

Connection

Spring force terminals

RS232-cable length

max. 15 m

LOW signal voltage

-18 V ... -3 V

HIGH signal voltage

3 V ... 18 V

Power supply

via K-Bus

Electrical isolation

500 Vrms (K-Bus / signal voltage)

Data buffer

128 byte receive buffer, 16 byte transmit buffer

Bit width in the Process image

I/O: 3 x 8 bits user data, 1 x 8 bits control/status (up to 5 x 8 bits user
data possible)

Configuration

no address setting, configuration setting via the bus coupler or control
system

Current consumption from K-Bus

55 mA

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Relative humidity

95%, no condensation

Vibration/shock resistance

conforms to IEC 68-2-6 / IEC 68-2-27

EMC resistance Burst / ESD

conforms to EN 50082 (ESD, Burst) / EN 50081

Installation position

any

Type of protection

IP20