5 the fail-safe principle (fail stop) – BECKHOFF KL6904 User Manual

Page 13

Advertising
background image

System description

KL6904

11

TwinSAFE digital input (KL1904) and output terminal (KL2904)

All current safety sensors can be connected

Operation with a TwinSAFE logic terminal

KL1904 with 4 fail-safe inputs for sensors (24 V

DC

) with floating contacts

KL2904 with four safe channels for actuators (24 V

DC

, 0.5 A per channel)

conforming to IEC 61508:2010 SIL 3

2.2.3 KL1904, KL2904 – Bus Terminals with 4 fail-safe inputs or outputs

The KL1904 and KL2904 Bus Terminals enable connection of common safety sensors and actuators.
They are operated with the KL6904 TwinSAFE logic terminal. The TwinSAFE logic terminal is the link unit
between the TwinSAFE input and output terminals. It enables the configuration of a simple, flexible and
cost-effective decentralized safety control system.

Therefore, there are no safety requirements for the higher-level controller! The typical safety functions
required for the automation of machines, such as emergency stop, protective door, two-hand etc., are
already permanently programmed in the KL6904. The user configures the KL6904 terminal according to
the safety requirements of his application.

2.2.4 KL6904 TwinSAFE logic terminal with 4 fail-safe outputs

The KL6904 TwinSAFE logic terminal is a digital output terminal with four fail-safe outputs with 0.5 A,
24 V

DC

. The KL6904 meets the requirements of IEC 61508:2010 SIL 3 and

DIN EN ISO 13849-1:2006 (Cat 4, PL e).

2.2.5 The fail-safe principle (Fail Stop)

The basic rule for a safety system such as TwinSAFE is that failure of a part, a system component or the
overall system must never lead to a dangerous condition. The safe state is always the switched off and
wattless state.