KL6904

45

4.3.1.3

Diag 3 (red) and Diag 4 (red)

The Diag 3 and Diag 4 LEDs indicate internal terminal errors.

Note

Returning the terminal

These errors lead to shutdown of the terminal. The terminal must be checked by
Beckhoff Automation GmbH & Co. KG.

Diag 3 LED (red)

Diag 4 LED (red)

Source of error

lit

flashing

µC1

lit

off

µC2

In the event of a fault the Diag 4 LED indicates the type of error through flashing codes. The flashing
codes are structured as follows:

Flashing sequence

Meaning

Rapid flickering

Start of flashing code

First slow sequence

Error code

Second slow sequence

Error code argument

Start

Error code

Error code argument

Count the number of flash pulses after the rapid flickering sequence

during the first slow sequence in order to ascertain the error code

during the second slow sequence in order to ascertain the error argument

The flashing code is repeated after the second slow sequence, followed by rapid flickering.